Brand Telemecanique Sensors
MFR# XCSPA591

TELEMECANIQUE SENSORS Safety Interlock Switch, 240V AC, 10 A, XCSPA Series XCSPA591

Country of Origin Multiple
Item Safety Interlock Switch
Series XCSPA
Head Material PA (polyamide)

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

Safety Interlock Switch, Series XCSPA

Technical Specifications

Country of Origin Multiple
Item Safety Interlock Switch
Series XCSPA
Head Material PA (polyamide)
Body Material PA (polyamide)
Material plastic
Standards EN/IEC 60947-5-1 || CSA C22.2 No 14 || EN/ISO 12100 || EN/IEC 60204-1 || EN 1088/ISO 14119 || UL 508
Electrical Connection terminal 1 x 0.5...2 x 1.5 mm² with or without cable end
Head Type key operated turret head
Mechanical Durability 1000000 cycles
Shock Resistance 10 gn 11 ms IEC 60068-2-27
Vibration Resistance 5 gn 10-500 Hz)IEC 60068-2-6
Contacts Type And Composition 1 NC + 1 NO
Positive Opening Minimum Force 15 N
[Ie] Rated Operational Current 6 A 120 V, AC-15, A300 EN/IEC 60947-5-1 || 3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q300 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1
[Ithe] Conventional Enclosed Thermal Current 10A
Minimum Actuation Speed 0.01 m/s
Ip Degree Of Protection IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Cable Entry 1 entry tapped Pg 11
Design compact
Product Or Component Type safety switch
Protective Treatment TC
Contact Operation slow-break, break before make
Short-Circuit Protection 10 A cartridge fuse gG (gl)
Actuator Forcible Withdrawal Rtc 10 N
Product Certifications UL || CSA
Maximum Operating Rate 10 cyc/mn for maximum durability
Positive Opening with NC contact
[Uimp] Rated Impulse Withstand Voltage 6 kV EN/IEC 60947-5-1
Electrical Shock Protection Class class II EN/IEC 61140