Part of the NOVA Platform ecosystem · Kampala, Uganda · sales@redgroundonline.com · WhatsApp +256 755 978 947
ℹ About ❓ How it Works ✉ Contact 🔑 Sign In
Submit RFQ Request →
Categories
Sub-Categories
Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Switches → Safety Switches → TELEMECANIQUE SENSORS Emergency Cable Pull Switch, 2NO/2NC XY2CEDA196H7
TELEMECANIQUE SENSORS Emergency Cable Pull Switch, 2NO/2NC XY2CEDA196H7
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Telemecanique Sensors
MFR# XY2CEDA196H7

TELEMECANIQUE SENSORS Emergency Cable Pull Switch, 2NO/2NC XY2CEDA196H7

Country of Origin Morocco
Item Emergency Cable Pull Switch
AC Contact Rating 3 A @ 240 V
Contact Form 2NO/2NC

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

Emergency Cable Pull Switch, AC Contact Rating 3 A @ 240 V, Contact Form 2NO/2NC, Push Button Reset, Cable Connection Location Left and Right, Thermal Amperage 10 A, Length 12.89 in, 13.21 in, Width 3.82 in, 4.17 in, Depth 5.59 in, Switching Ability Dual Cable, DC Contact Rating 0.27 A @ 250 V, Case Material Stainless Steel, Wiring Entry 1/2 in NPT, IP Rating IP66

Technical Specifications

Country of Origin Morocco
Item Emergency Cable Pull Switch
AC Contact Rating 3 A @ 240 V
Contact Form 2NO/2NC
Reset Push Button
Switching Ability Dual Cable
DC Contact Rating 0.27 A @ 250 V
Body Material zamak
Wiring Entry 1/2 in NPT
Series XY2C
IP Rating IP66
Standards CCC, CSA, CSA C22.2 No. 14 Machinery Directive 2006/42/EC, EN/IEC 60204-1, EN/IEC 60947-5, EN/IEC 60947-5-5, EN/ISO 13850, UL 508, Work Equipment Directive 2009/104/EC
Case Material Stainless Steel
Cable Connection Location Left and Right
Thermal Amperage 10 A
Protective Treatment TC
[Uimp] Rated Impulse Withstand Voltage 6 kV EN/IEC 60947-1
Cable Entry Number 3 tapped entry 1/2" NPT conduit entry
Positive Opening with EN/IEC 60947-5-1
Tightening Torque 0.8-1.2 N.m
Ip Degree Of Protection IP66 IEC 60529
Contacts Type And Composition 2 x (1 NC + 1 NO)
Contact Operation slow-break
Device Short Name XY2CED
[Ie] Rated Operational Current 3 A 240 V, AC-15, A300 EN/IEC 60947-5-1 appendix A || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 appendix A
Connections - Terminals screw clamp terminal, 1 x 0.5 to 2 x 1.5 mm²
Cover Material stainless steel
Housing Colour red RAL 3000
Overvoltage Category class I EN/IEC 61140
Distance Between Cable Supports 3-5 m