Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Motor Starters, Enclosures & Accessories → SQUARE D Manual Motor Starter, 3 P, 3 Phase, Selector Switch, 0.40 A GV2P03
SQUARE D Manual Motor Starter, 3 P, 3 Phase, Selector Switch, 0.40 A GV2P03
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Square D
MFR# GV2P03

SQUARE D Manual Motor Starter, 3 P, 3 Phase, Selector Switch, 0.40 A GV2P03

Country of Origin Thailand
Item Manual Motor Starter
Number of Poles 3
Operator Selector Switch

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

Manual Motor Starter, NEMA Size Not Applicable, Maximum Voltage Rating 600V AC, Number of Poles 3, Operator Selector Switch, Phase Three, Current AC 0.4 A, Series TeSys Deca, Maximum Overload Relay Current Setting 0.4 A, Minimum Overload Relay Current Setting 0.25 A, NEMA Enclosure Rating No Enclosure, Overload Protection Type Thermal, Starter Style IEC, Terminal Connection Type Screw Clamp Terminals, IP Rating IP20, Resistance Properties Fire Resistant, Frequency 50/60 Hz, Overall Depth 3.82 in

Technical Specifications

Country of Origin Thailand
Item Manual Motor Starter
Number of Poles 3
Operator Selector Switch
Phase 3
Current AC 0.40 A
Series TeSys Deca
Standards ATEX Compliant, BV, CCC, CSA, DNV-GL, EAC, EN/IEC 60947-2, EN/IEC 60947-4, LROS, RINA, UKCA, UL Listed
Description/Special Features Screw Clamp Terminals, Single Unit
Pilot Light No
Phase Loss Sensitivity Yes
Range TeSys Deca
Power Dissipation Per Pole 2.5 W
Suitability For Isolation yes IEC 60947-1§ 7-1-6
Mechanical Robustness shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Fixing Mode 35 mm symmetrical DIN rail clipped || panel screwed with 2 x M4 screws)
Motor Power Kw 0.09-0.09 kW 400/415 V AC 50/60 Hz
Utilisation Category category A IEC 60947-2 || AC-3 IEC 60947-4-1
Tightening Torque 1.7 N.m screw clamp terminal
Device Short Name GV2P
Phase Failure Sensitivity yes IEC 60947-4-1
Climatic Withstand IACS E10
Magnetic Tripping Current 5-5 A
Network Type AC
Operating Altitude 6561.68 ft (2000 m)
Ambient Air Temperature For Storage -40-80°C
Ik Degree Of Protection IK04
Device Application motor protection
Trip Unit Technology thermal-magnetic
Thermal Protection Adjustment Range 0.25-0.4 A IEC 60947-4-1