Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Motor Starters, Enclosures & Accessories → SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, Toggle, 10 A GV2RT14
SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, Toggle, 10 A GV2RT14
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# GV2RT14

SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, Toggle, 10 A GV2RT14

Country of Origin Korea, Republic of
Item Manual Motor Starter
Number of Poles 3
Operator Toggle

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

Manual Starter 600Vac 10Amp Iec

Technical Specifications

Country of Origin Korea, Republic of
Item Manual Motor Starter
Number of Poles 3
Operator Toggle
Phase 3
Current AC 10 A
Series TeSys Deca
Standards EN/IEC 60947-2 || EN/IEC 60947-4-1
Fixing Mode 35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-2
Ambient Air Temperature For Storage -40-80°C
Product Name TeSys GV2 || TeSys Deca
Operating Altitude 6561.68 ft (2000 m)
Tightening Torque 1.7 N.m screw clamp terminal
Rated Duty continuous IEC 60947-4-1
Climatic Withstand IACS E10
Power Dissipation Per Pole 2.5 W
Utilisation Category category A IEC 60947-2 || AC-3 IEC 60947-4-1
Ik Degree Of Protection IK04
Network Type AC
Device Short Name GV2RT
Motor Power Kw 1.5-1.5 kW 220/230 V AC 50/60 Hz motor protection high peak current || 2.2-2.2 kW 220/230 V AC 50/60 Hz motor protection high peak current || 3-3 kW 400/415 V AC 50/60 Hz motor protection high peak current || 4-4 kW 400/415 V AC 50/60 Hz motor protection high peak current || 4-4 kW 440 V AC 50/60 Hz motor protection high peak current || 4-4 kW 500 V AC 50/60 Hz motor protection high peak current || 5.5-5.5 kW 500 V AC 50/60 Hz motor protection high peak current || 5.5-5.5 kW 690 V AC 50/60 Hz motor protection high peak current || 7.5-7.5 kW 690 V AC 50/60 Hz motor protection high peak current || 2.5-2.5 kW 230/240 V AC 50/60 Hz transformer protection || 4-4 kW 400/415 V AC 50/60 Hz transformer protection || 5-5 kW 400/415 V AC 50/60 Hz transformer protection || 5-5 kW 440 V AC 50/60 Hz transformer protection || 5-5 kW 500 V AC 50/60 Hz transformer protection || 6.3-6.3 kW 500 V AC 50/60 Hz transformer protection
Fire Resistance 960°C IEC 60695-2-11
Range TeSys Deca
Thermal Protection Adjustment Range 6-10 A IEC 60947-4-1
Suitability For Isolation yes IEC 60947-1§ 7-1-6
Mechanical Robustness shocks 30 Gn for 11 ms || vibrations 5 Gn, 5 to 150 Hz
Trip Unit Technology thermal-magnetic
Device Application motor protection || motor
Magnetic Tripping Current 200-200 A