Part of the NOVA Platform ecosystem · Kampala, Uganda · sales@redgroundonline.com · WhatsApp +256 755 978 947
ℹ About ❓ How it Works ✉ Contact 🔑 Sign In
Submit RFQ Request →
Categories
Sub-Categories
Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Motor Starters, Enclosures & Accessories → SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, Rotary Handle, 18 A GV3P18
SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, Rotary Handle, 18 A GV3P18
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# GV3P18

SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, Rotary Handle, 18 A GV3P18

Country of Origin Korea, Republic of
Item Manual Motor Starter
Number of Poles 3
Operator Rotary Knob

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

Manual Starter 600Vac 40Amp Iec

Technical Specifications

Country of Origin Korea, Republic of
Item Manual Motor Starter
Number of Poles 3
Operator Rotary Knob
Current AC 18 A
Series TeSys Deca
Standards EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Color dark grey
Fire Resistance 960°C IEC 60695-2-11
Rated Duty continuous IEC 60947-4-1
Fixing Mode 35 mm symmetrical DIN rail clipped || panel screwed with 3 x M4 screws)
Device Short Name GV3P
Suitability For Isolation yes IEC 60947-1
Ambient Air Temperature For Storage -40-80°C
Motor Power Kw 7.5-7.5 kW 400/415 V AC 50/60 Hz || 9-9 kW 500 V AC 50/60 Hz || 15-15 kW 690 V AC 50/60 Hz
Operating Altitude 9842.52 ft (3000 m)
Product Name TeSys GV3 || TeSys Deca
Thermal Protection Adjustment Range 12-18 A IEC 60947-4-1
Climatic Withstand IACS E10
Network Type AC
Power Dissipation Per Pole 8 W
Trip Unit Technology thermal-magnetic
Tightening Torque 5 N.m screw clamp terminal
Magnetic Tripping Current 252-252 A
Range TeSys Deca
Mechanical Robustness shocks 15 Gn for 11 ms contactor open || shocks 30 Gn for 11 ms contactor closed || vibrations 4 Gn, 5 to 300 Hz
Phase Failure Sensitivity yes IEC 60947-4-1
Device Application motor protection
Utilisation Category AC-3 IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-2
Can't find it?
We source what you need.
Bookmarks
Recently Viewed
Compare