Part of the NOVA Platform ecosystem · Kampala, Uganda · sales@redgroundonline.com · WhatsApp +256 755 978 947
ℹ About ❓ How it Works ✉ Contact 🔑 Sign In
Submit RFQ Request →
Categories
Sub-Categories
Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Motor Starters, Enclosures & Accessories → SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, 3 Phase, Push Button, 10 A GV2ME14
SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, 3 Phase, Push Button, 10 A GV2ME14
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# GV2ME14

SCHNEIDER ELECTRIC Manual Motor Starter, 3 P, 3 Phase, Push Button, 10 A GV2ME14

Country of Origin Thailand
Item Manual Motor Starter
Number of Poles 3
Operator Push Button

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

Manual Motor Starter, NEMA Size Not Applicable, Horsepower @ Single Phase - 120V AC 1/2 hp, Horsepower @ Single Phase - 240V AC 1 1/2 hp, Maximum Voltage Rating 690V AC, Number of Poles 3, Operator Push Button, Phase Three, Current AC 10 A, Horsepower @ Three Phase - 208V AC 2 hp, Horsepower @ Three Phase - 240V AC 3 hp, Horsepower @ Three Phase - 480V AC 5 hp, Series TeSys Deca, Horsepower @ Three Phase - 600V AC 7 1/2 hp, Maximum Overload Relay Current Setting 10 A

Technical Specifications

Country of Origin Thailand
Item Manual Motor Starter
Number of Poles 3
Operator Push Button
Phase 3
Current AC 10 A
Series TeSys Deca
Standards ATEX Compliant, BV, CCC, CSA, DNV-GL, EAC, EN/IEC 60947-2, EN/IEC 60947-4, LROS, RINA, UKCA, UL Listed
Pilot Light No
Description/Special Features Melting Alloy Thermal Overload, Single Unit
HP @ 3 Phase - 460-575V 5/7.5
HP @ 3 Phase - 575V 7 1/2 hp
HP @ 1 Phase - 230V 1 1/2 hp
Phase Loss Sensitivity Yes
Fire Resistance 960°C IEC 60695-2-11
Magnetic Tripping Current 138-138 A
Climatic Withstand IACS E10
Power Dissipation Per Pole 2.5 W
Phase Failure Sensitivity yes IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-2
Motor Power Kw 3-3 kW 400/415 V AC 50/60 Hz || 4-4 kW 400/415 V AC 50/60 Hz || 4-4 kW 500 V AC 50/60 Hz || 5.5-5.5 kW 500 V AC 50/60 Hz || 5.5-5.5 kW 690 V AC 50/60 Hz || 7.5-7.5 kW 690 V AC 50/60 Hz
Thermal Protection Adjustment Range 6-10 A IEC 60947-4-1
Utilisation Category category A IEC 60947-2 || AC-3 IEC 60947-4-1
Ambient Air Temperature For Storage -40-80°C
Device Application motor protection
Ik Degree Of Protection IK04
Mechanical Robustness shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Rated Duty continuous IEC 60947-4-1
Range TeSys Deca
Network Type AC
Can't find it?
We source what you need.
Bookmarks
Recently Viewed
Compare