Brand Square D
MFR# LUCA32FU

SQUARE D OVERLOAD RELAY AND CONTROL LUCA32FU

Country of Origin Mexico
Item Overload Relay
Minimum Overload Relay Current Setting 8 A
Maximum Overload Relay Current Setting 32 A

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Technical Specifications

Country of Origin Mexico
Item Overload Relay
Minimum Overload Relay Current Setting 8 A
Maximum Overload Relay Current Setting 32 A
Trip Class 10
Maximum Voltage Rating 690 V
Standards CSA,UL 489
Application overload and short-circuit
Control Circuit Voltage Limits 88 to 264 V AC 110 to 240 V in operation; 88 to 242 V DC 110 to 220 V in operation; 55 V AC 110 to 240 V drop-out; 55 V DC 110 to 220 V drop-out
Compatibility Code LUCA
Network Frequency 40 to 60 Hz
Rated Motor Current Adjustment Range 8 to 32 A
Immunity To Voltage Dips 70% / 500 ms IEC 61000-4-11
Main Function Available Earth fault protection; Protection against phase failure and phase imbalance; Protection against overload and short-circuit; Manual reset
Rated Insulation Voltage 690 V IEC 60947-6-2; 600 V UL 60947-4-1; 600 V CSA C22.2 No 60947-4-1
Ambient Air Temperature For Operation -13 to 158°F (-25 to 70°C)
Product Or Component Type Standard control unit
Tripping Threshold 14.2 x Ir +/- 20%
Control Circuit Voltage 110 to 240 V AC; 110 to 220 V DC
IP Degree Of Protection IP20 front panel and wired terminals IEC 60947-1; IP20 other faces IEC 60947-1; IP40 front panel outside connection zone IEC 60947-1
Heat Dissipation 3 W control circuit with LUB32; 3 W control circuit with LUB38
Vibration Resistance 2 gn 5 to 300 Hz power poles open IEC 60068-2-6; 4 gn 5 to 300 Hz power poles closed IEC 60068-2-6
Shock Resistance 10 gn power poles open IEC 60068-2-27; 15 gn power poles closed IEC 60068-2-27
Utilisation Category AC-43; AC-41; AC-44
Product Name TeSys Ultra
Resistance To Electrostatic Discharge 8 kV 3 in open air IEC 61000-4-2; 8 kV 4 on contact IEC 61000-4-2
Rated Impulse Withstand Voltage 6 kV IEC 60947-6-2
Fire Resistance 1760°F (960°C) parts supporting live components IEC 60695-2-12; 1202°F (650°C) IEC 60695-2-12
Immunity To Microbreaks 3 ms
Fixing Mode Plug-in front face)