SCHNEIDER ELECTRIC Thermal Overload Relay, 1NC/1NO, 4 A Min current, 6 A Max current LRD106
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand
Schneider Electric
MFR#
LRD106
SCHNEIDER ELECTRIC Thermal Overload Relay, 1NC/1NO, 4 A Min current, 6 A Max current LRD106
Country of Origin
France
Item
Thermal Overload Relay
Auxiliary Contact Form
1NC/1NO
Minimum Overload Relay Current Setting
4:00 AM
Search Similar Products
Uncheck any specs you want to ignore
Description
Bimetallic Overload Relay 600V 6A Iec
Technical Specifications
Country of Origin
France
Item
Thermal Overload Relay
Auxiliary Contact Form
1NC/1NO
Minimum Overload Relay Current Setting
4:00 AM
Maximum Overload Relay Current Setting
6:00 AM
Trip Class
10A
Overload Protection Type
Thermal
Maximum Voltage Rating
1,000V
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
Flame Retardance
V1 conforming to UL 94
Associated Fuse Rating
4 A gG signalling circuit || 4 A BS signalling circuit
Network Frequency
0 to 400 Hz
Ambient Air Temperature For Storage
-60-70°C
Tightening Torque
control circuit 1.7 N.m screw clamp terminals || power circuit 2.3 N.m lugs-ring terminals M4
Connections - Terminals
control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit lugs-ring terminals
Device Short Name
LRD
Control Type
Red push-button stop || Blue push-button reset
Product Name
TeSys LRD || TeSys Deca
Thermal Protection Adjustment Range
4-6 A
Tripping Threshold
1.14 +/- 0.06 Ir IEC 60947-4-1
Permissible Current
3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
Mechanical Robustness
vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
Product Or Component Type
differential thermal overload relay
Phase Failure Sensitivity
tripping current 130 % of Ir on two phase, the last one at 0
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Network Type
AC || DC
Range
TeSys || TeSys Deca
Connection Pitch
14.5 mm
Ambient Air Temperature For Operation
-20-60°C without derating IEC 60947-4-1
Relay Application
motor protection
Similar Products
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 12 A Min current, 18 A Max current, 690V AC LRD21
LRD21
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 23 A Min current, 32 A Max current, 690V AC LRD32
LRD32
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 4 A Min current, 6 A Max current, 690V AC LRD10
LRD10
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 16 A Min current, 24 A Max current, 690V AC LRD22
LRD22
Goodman
GOODMAN Overload Protector, Green Overload Protector, 2 in 60349605A
60349605A
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 2.5 A Min current, 4 A Max current, 690V AC LRD08
LRD08
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 7 A Min current, 10 A Max current, 690V AC LRD14
LRD14
Siemens
SIEMENS Overload Relay, 1NC/1NO, 50 A Min current, 200 A Max current, 690V AC 3UB81334HW2
3UB81334HW2
Can't find it?
We source what you need.