Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Motor Overload Relays → SCHNEIDER ELECTRIC TeSys Deca thermal overload relays, 37.50A, class 20 LR3D3557
SCHNEIDER ELECTRIC TeSys Deca thermal overload relays, 37.50A, class 20 LR3D3557
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# LR3D3557

SCHNEIDER ELECTRIC TeSys Deca thermal overload relays, 37.50A, class 20 LR3D3557

Country of Origin France
Item Overload Relay
Auxiliary Contact Form 1NC/1NO
Minimum Overload Relay Current Setting 37 A

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

3750A Class 20 Iec Overload Relay

Technical Specifications

Country of Origin France
Item Overload Relay
Auxiliary Contact Form 1NC/1NO
Minimum Overload Relay Current Setting 37 A
Maximum Overload Relay Current Setting 50 A
Trip Class 20
Overload Protection Type Thermal
Maximum Voltage Rating 1,000V
Standards EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
Control Type Red push-button stop || Blue push-button reset
Thermal Protection Adjustment Range 37-50 A
Range TeSys
Tripping Threshold 1.14 +/- 0.06 Ir IEC 60947-4-1
Dielectric Strength 1.89 kV 50 Hz IEC 60947-1
Ambient Air Temperature For Storage -60-70°C
Device Short Name LR3D
Product Compatibility LC1D95 || LC1D80
Tightening Torque control circuit 1.7 N.m screw clamp terminals || power circuit 9 N.m screw clamp terminals
Thermal Overload Class class 20 IEC 60947-4-1
Product Name TeSys LRD || TeSys Deca
Ambient Air Temperature For Operation -20-60°C without derating IEC 60947-4-1
Associated Fuse Rating 4 A gG signalling circuit || 4 A BS signalling circuit
Phase Failure Sensitivity tripping current 130 % of Ir on two phase, the last one at 0
Flame Retardance V1 conforming to UL 94
Product Certifications IEC || UL || CSA || CCC || EAC || BV || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Network Frequency 0 to 400 Hz
Network Type AC || DC
Connections - Terminals power circuit screw clamp terminals 1 4-35 mm² flexible without cable end || power circuit screw clamp terminals 1 4-35 mm² flexible with cable end || power circuit screw clamp terminals 1 4-35 mm² solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end
Mechanical Robustness vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7