SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 90 A Min current, 150 A Max current LR9D5569
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand
Schneider Electric
MFR#
LR9D5569
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 90 A Min current, 150 A Max current LR9D5569
Country of Origin
Korea, Republic of
Item
Overload Relay
Auxiliary Contact Form
1NC/1NO
Minimum Overload Relay Current Setting
90 A
Search Similar Products
Uncheck any specs you want to ignore
Description
Solid State Overload Relay 575Vac 150A
Technical Specifications
Country of Origin
Korea, Republic of
Item
Overload Relay
Auxiliary Contact Form
1NC/1NO
Minimum Overload Relay Current Setting
90 A
Maximum Overload Relay Current Setting
150 A
Trip Class
20
Overload Protection Type
Electronic
Maximum Voltage Rating
24V DC
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5
Relay Application
motor protection
Signalling Function
alarm
Control Type
Red push-button stop || Blue push-button reset
Supply Voltage Limits
17-32 V
Connections - Terminals
power circuit bars || control circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end || control circuit screw clamp terminals 2 0.5-1.5 mm² flexible without cable end || alarm circuit screw clamp terminals 1 0.5-1.5 mm² flexible without cable end
Thermal Overload Class
class 20 IEC 60947-4-1
Thermal Protection Adjustment Range
90-150 A
Network Type
AC
Range
TeSys
Switching Capacity In Ma
0 to 150 mA
Associated Fuse Rating
4 A gG signalling circuit || 4 A BS signalling circuit
Climatic Withstand
IACS E10
Mechanical Robustness
vibrations2 Gn, 5 to 300 Hz IEC 60068-2-6 || shocks13 Gn for 11 ms IEC 60068-2-7
Product Or Component Type
electronic thermal overload relay
Ambient Air Temperature For Operation
-20-60°C without derating IEC 60947-4-1
Ambient Air Temperature For Storage
-60-70°C
Network Frequency
50-60 Hz
Product Name
TeSys LRD || TeSys Deca
Phase Failure Sensitivity
tripping in 4 s +/- 20 % IEC 60947-4-1
Tripping Threshold
1.05 +/- 0.06 In alarm IEC 60947-4-1 || 1.12 +/- 0.06 In de-energisation IEC 60947-4-1
Maximum Voltage Drop
<2.5 V closed state
Similar Products
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 12 A Min current, 18 A Max current, 690V AC LRD21
LRD21
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 23 A Min current, 32 A Max current, 690V AC LRD32
LRD32
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 4 A Min current, 6 A Max current, 690V AC LRD10
LRD10
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 16 A Min current, 24 A Max current, 690V AC LRD22
LRD22
Goodman
GOODMAN Overload Protector, Green Overload Protector, 2 in 60349605A
60349605A
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 2.5 A Min current, 4 A Max current, 690V AC LRD08
LRD08
Schneider Electric
SCHNEIDER ELECTRIC Overload Relay, 1NC/1NO, 7 A Min current, 10 A Max current, 690V AC LRD14
LRD14
Siemens
SIEMENS Overload Relay, 1NC/1NO, 50 A Min current, 200 A Max current, 690V AC 3UB81334HW2
3UB81334HW2
Can't find it?