Part of the NOVA Platform ecosystem · Kampala, Uganda · sales@redgroundonline.com · WhatsApp +256 755 978 947
ℹ About ❓ How it Works ✉ Contact 🔑 Sign In
Submit RFQ Request →
Categories
Sub-Categories
Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Electrical Contactors & Contacts → SCHNEIDER ELECTRIC IEC Miniature Magnetic Contactor, 2NC, 120V AC, 3 P, Reversing, Screw Clamp LC2K0901G7
SCHNEIDER ELECTRIC IEC Miniature Magnetic Contactor, 2NC, 120V AC, 3 P, Reversing, Screw Clamp LC2K0901G7
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# LC2K0901G7

SCHNEIDER ELECTRIC IEC Miniature Magnetic Contactor, 2NC, 120V AC, 3 P, Reversing, Screw Clamp LC2K0901G7

Country of Origin Korea, Republic of
Item IEC Miniature Magnetic Contactor
Auxiliary Contact Form 1NC
Coil Voltage 120V AC

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

The IEC Miniature Magnetic Contactor is a 3-pole reversing contactor from the TeSys K series. It uses a 120 V AC coil to switch low- to medium-power circuits for motor control and resistive loads. The device is rated for operation with DIN rail or plate mounting options and is compatible with screw clamp terminal connections. It is equipped with auxiliary contacts configured as 2 NC contacts.

Action: Reversing function available for motor control applications

  • Poles: 3
  • Coil Voltage: 120 V AC
  • Series/Style: TeSys K, IEC
  • Mounting Style: DIN Rail, Plate
  • Electrical Connection: Compatible with screw clamp terminal connections
  • Auxiliary Contacts: Equipped; Configuration: 2 NC contacts
  • Frequency: 50/60 Hz
  • IP Rating: IP20
  • Maximum Voltage Rating: Rated for operation up to 690 V AC within specified conditions
  • Rated Making Capacity: 110 A under specified test conditions
  • Withstand ratings: Based on standardized testing parameters and do not imply guaranteed performance under all conditions
  • Electrical durability: Based on standardized testing cycles and may vary with actual usage conditions
  • Mechanical durability: Based on standardized testing cycles and may vary with actual usage conditions
  • Rated Voltage: 690 V AC
  • Impedance: Typical impedance value measured under test conditions; actual impedance may vary slightly in application
  • Impulse Withstand Voltage: Rated impulse withstand voltage according to standards; does not guarantee protection against all transient events
  • Inrush VA / Hold VA / Max Operating Watts: Power consumption figures are nominal values based on standard tests and may differ during actual operation
  • Fuse Amps: 25 A (Power Circuit), 10 A (Signalling Circuit)
  • Net Weight: 0.39 kg
  • Width/Depth/Height: Width 2.5 in; Overall Width 3.54 in; Depth 3.6 in; Overall Depth 2.24 in; Height 2.5 in; Overall Height 2.28 in
  • Enclosure: No Enclosure; NEMA Enclosure Rating: No Enclosure
  • Fire Rating: UL 94 V1; NF F 16-101; NF F 16-102
  • Standards: BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
  • Signalling Circuit Frequency: Less Than 400 Hz
  • Shock Resistance: 10 G (11 ms) X axis (Closed); 15 G (11 ms) Y/Z axis (Closed); 6 G (11 ms) X axis (Open); 10 G (11 ms) Y/Z axis (Open)
  • Operating Temperature: Maximum 122 °F; Minimum -13 °F
  • Reversing: Yes
  • Technical Specifications

    Country of Origin Korea, Republic of
    Item IEC Miniature Magnetic Contactor
    Auxiliary Contact Form 1NC
    Coil Voltage 120V AC
    Number of Poles 3
    Full Load Amps-Inductive 9 A
    Full Load Amps-Resistive 20 A
    Reversing Capability Reversing
    Terminal Connection Type Screw Clamp
    Number of Auxillary Contacts 1
    Standards BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
    Enclosure NEMA Rating No Enclosure
    HP @ 1 Phase - 230V 1-1/2
    Reversing Yes
    HP @ 3 Phase - 575V 5 hp
    Series TeSys K
    Control Circuit Voltage Limits Operational: 0.8 to 1.15 Uc (at 50°C), Drop-Out: 0.2 to 0.75 Uc (at 50°C)
    Rated Insulation Volts 600V, 690V
    IP Rating IP20
    Insulation Resistance Range Greater Than 10 MOhms (Signalling Circuit)
    Switching Current 5 mA (Signalling Circuit)
    Inrush VA 30 VA
    Impedance 3 mOhm
    Signalling Circuit Frequency Less Than 400 Hz
    Fire Rating UL 94 V1, NF F 16-101, NF F 16-102
    Operating Time 10 to 20 ms (Coil Energisation and NO Closing), 10 to 20 ms (Coil De-Energisation and NO Opening)
    Vibration Resistance 4 G (Contactor Closed), 2 G (Contactor Open)
    Electrical Durability 0.18 Mcycles (20 A, AC-1, Less than 440 V); 1.3 Mcycles (9 A, AC-3, Less than 440 V); 1.3 Mcycles (9 A, AC-3e, Less than 440 V)
    Mechanical Durability 5 Mcycles
    Fuse Amps 25 A (Power Circuit), 10 A (Signalling Circuit)