SCHNEIDER ELECTRIC IEC Magnetic Contactor, 1NO, 120V AC, 3 P, Non-Reversing, Screw Clamp DPE25G7
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# DPE25G7

SCHNEIDER ELECTRIC IEC Magnetic Contactor, 1NO, 120V AC, 3 P, Non-Reversing, Screw Clamp DPE25G7

Country of Origin Indonesia
Item IEC Magnetic Contactor
Auxiliary Contact Form 1NO
Coil Voltage 120V AC

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

The Schneider Electric IEC Magnetic Contactor is a TeSys Easy, IEC-style three-pole magnetic switch designed for power control in electrical systems. It features a 120 V AC coil, is non-reversing, and includes 1 normally open auxiliary contact. The device uses screw clamp terminals and is suited for motor control and resistive load applications, rated for operation at voltages up to 690 V AC within the specified frequency range.

Key features

  • Poles and contacts: 3 poles; 3 normally open main contacts; 0 normally closed main contacts; auxiliary contact 1 NO (Includes auxiliary contacts: Yes)
  • Coil and control: Coil voltage 120 V AC; Reversing: Non-Reversing
  • Electrical ratings: Rated voltage up to 690 V AC; Rated insulation 600/690 V; Full Load Amps 25 A (resistive); 25 A (inductive)
  • Making capacity: 140 A (AC Signalling), 250 A (DC Signalling), 300 A @ 440 V (Power Circuit)
  • Connection and mounting: Screw Clamp terminals; Mounting: DIN Rail, Plate; Mounts on Plate, Rail; IP20; No Enclosure
  • Physical size and weight: Height 3.03 in; Width 1.77 in; Depth 3.39 in; Net weight 0.33 kg
  • Durability: Electrical durability tested according to applicable standards; actual lifespan may vary based on usage conditions
  • Standards: CSA, CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL Listed, UL 60947-4-1
  • Additional specs: Impedance 2.5 mΩ; Impulse withstand voltage 6 kV; Signalling frequency 25–400 Hz; Signalling current 5 mA; Switching voltage (signalling circuit) up to approximately 17 V; Special features include without built-in suppressor module and overvoltage category III
  • Environmental and design notes: Max temperature 85°C; Series: TeSys Easy
  • Technical Specifications

    Country of Origin Indonesia
    Item IEC Magnetic Contactor
    Auxiliary Contact Form 1NO
    Coil Voltage 120V AC
    Number of Poles 3
    Full Load Amps-Inductive 25 A
    Full Load Amps-Resistive 25 A
    Reversing Capability Non-Reversing
    Terminal Connection Type Screw Clamp
    Number of Auxillary Contacts 1
    Standards CSA, CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL Listed, UL 60947-4-1
    Enclosure NEMA Rating 3R; 4
    Reversing No
    HP @ 3 Phase - 575V 15 hp
    Frame / Series / Class / Code TeSys
    Special Features Overvoltage Category III; Minimum Switching Voltage 17 V Signalling Circuit; Insulation Resistance 10 MOhm Signalling Circuit
    Features Without Built-In Suppressor Module
    Application Motor Control, Resistive Load
    Hold VA 7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
    Control Circuit Voltage Limits Drop-Out: 0.3 to 0.6 Uc (at 70°C 50/60 Hz); Operational: 0.8 to 1.1 Uc (at 60°C 50 Hz 0.85 to 1.1 Uc (at 60°C 60 Hz), 1 to 1.1 Uc (at 70°C 50/60 Hz)
    Environmental Attributes Mercury Free, Toxic Heavy Metal Free, Pollution Degree 3
    Switching Current 5 mA (Signalling Circuit)
    Impulse Withstand Voltage 6 kV
    Rated Making Capacity 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 300 A @ 440V (Power Circuit)
    Net Weight 0.33 kg
    Electrical Durability 1 Mcycles (25 A, AC-3, Less than 440 V); 0.6 Mcycles (32 A, AC-1, Less than 440 V)
    Rated Insulation Volts 600V, 690V
    Tightening Torque 1.7 Nm
    Fuse Amps 10 A (Signalling Circuit), 50 A (Type 1 Power Circuit), 35 A (Type 2 Power Circuit)
    Insulation Resistance Range Greater Than 10 MOhms (Signalling Circuit)