Part of the NOVA Platform ecosystem · Kampala, Uganda · sales@redgroundonline.com · WhatsApp +256 755 978 947
ℹ About ❓ How it Works ✉ Contact 🔑 Sign In
Submit RFQ Request →
Categories
Sub-Categories
Home → Departments → Electrical Items → Industrial Electrical Controls & Automation → Electrical Controls → Electrical Contactors & Contacts → SCHNEIDER ELECTRIC IEC Magnetic Contactor, 1NC/1NO, 120V AC, 3 P, Non-Reversing, Screw Clamp LC1D09G7
SCHNEIDER ELECTRIC IEC Magnetic Contactor, 1NC/1NO, 120V AC, 3 P, Non-Reversing, Screw Clamp LC1D09G7
Verified Sourcing
Import & Local Stock
Flexible Payment
Brand Schneider Electric
MFR# LC1D09G7

SCHNEIDER ELECTRIC IEC Magnetic Contactor, 1NC/1NO, 120V AC, 3 P, Non-Reversing, Screw Clamp LC1D09G7

Country of Origin Indonesia
Item IEC Magnetic Contactor
Auxiliary Contact Form 1NC/1NO
Coil Voltage 120V AC

Specify quantity and delivery requirements when submitting your RFQ

WhatsApp Email

Description

The Schneider Electric IEC Magnetic Contactor is a 3-pole, non-reversing coil-operated switch rated for use in motor control and resistive load applications within specified parameters. It uses screw clamp terminals and features 1 normally open and 1 normally closed auxiliary contact (2 auxiliary contacts total). The unit is part of the TeSys Deca series, compatible with IEC-standard control panels, suitable for DIN rail or plate mounting as per specifications, and includes a protective cover; it does not include an enclosure or an embedded surge suppressor.

Poles: 3

  • Main contacts: 3 NO
  • Auxiliary contacts: 2 (1 NO / 1 NC)
  • Coil voltage: 120 V AC
  • Reversing: Non-Reversing
  • Series/Frame: TeSys Deca / TeSys
  • Mounting: DIN Rail, Plate
  • Electrical connection: Screw Clamp
  • Max voltage: 690 V AC; 300 V DC within specified limits
  • Frequency: 50/60 Hz
  • IP rating: IP20
  • Enclosure: No Enclosure
  • Protective cover: Yes
  • Standards: BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
  • Application: Intended for use in motor control and resistive load applications according to manufacturer specifications
  • Weight: 0.32 kg
  • Dimensions (approx.): Width 1.77 in, Height 3.03 in, Depth 3.38 in
  • Fire rating: UL 94 V1
  • Environmental traits: Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
  • Built-in suppressor: does not include a built-in surge suppression device; compatibility with external suppressors should be verified separately
  • Impulse withstand: rated for impulse withstand voltage of 6 kV under test conditions specified by standards
  • Hold/Inrush VA: Hold VA 7.5 VA; Inrush VA 70 VA
  • Operating speed/time: 3600 cycles per hr; 12–22 ms (Closing), 4–19 ms (Opening)
  • Mechanical durability: 15 Mcycles
  • Electrical durability: 2,000,000 (and 600,000) cycles indicated
  • Working temperature range: rated for operation within the specified temperature range of -40°F to 140°F (approx. -40°C to 60°C)
  • Shock/Vibration: tested according to applicable standards for shock and vibration levels; actual performance may vary based on application conditions
  • Auxiliary/Signalling: Includes Auxiliary Contacts; Signalling circuit frequency 25–400 Hz
  • Impedance: 2.5 mΩ
  • Rated making capacity: 250 A @ 440 V (Power Circuit), 140 A (AC Signalling), 250 A (DC Signalling)
  • Rated short-time withstand current: multiple values listed (e.g., 105–140 A depending on circuit)
  • Technical Specifications

    Country of Origin Indonesia
    Item IEC Magnetic Contactor
    Auxiliary Contact Form 1NC/1NO
    Coil Voltage 120V AC
    Number of Poles 3
    Full Load Amps-Inductive 9 A
    Full Load Amps-Resistive 20 A
    Reversing Capability Non-Reversing
    Terminal Connection Type Screw Clamp
    Number of Auxillary Contacts 2
    Standards BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
    HP @ 3 Phase - 575V 7 1/2 hp
    Enclosure NEMA Rating No Enclosure
    Frame / Series / Class / Code TeSys
    Reversing No
    Series TeSys Deca
    Mechanical Durability 15 Mcycles
    Watts Loss 2 to 3W
    Impedance 2.5 mOhm
    Signalling Circuit Frequency 25 to 400 Hz
    Rated Short-Time Withstand Current 105 A (at 40 Degrees C for 10 s Power Circuit), 210 A (at 40 Degrees C for 1 s Power Circuit), 30 A (at 40 Degrees C for 10 min Power Circuit), 61 A (at 40 Degrees C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
    Impulse Withstand Voltage 6 kV
    Rated Making Capacity 250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
    Application Motor Control, Resistive Load
    Net Weight 0.32 kg
    Control Circuit Voltage Limits Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz)
    Inrush VA 70 VA
    Non-Overlap Time 1.5 ms
    Includes Protective Cover Yes
    Switching Current 5 mA (Signalling Circuit)